Scheme link feature
Scheme link element is dedicated to dividing the scheme into logical blocks thus reducing graphics lag and allowing to calculate equivalents
A simple single-line diagram to simulate an arc flash scenario in one of the busses is created. System consists of 2 busses, transmission line between them and a fuse.
System parameters are provided at Table 1.
Arcing currents
Intermediate average arcing currents are defined using 1.1. equation:
where:
Ibf is the bolted fault current for three-phase faults (symmetrical rms) (kA)
Iarc_600 is the average rms arcing current at Voc = 600 V (kA);
Iarc_2700 is the average rms arcing current at Voc = 2700 V (kA);
Iarc_14300 is the average rms arcing current at Voc =14 300 V (kA);
G is the gap distance between electrodes (mm);
k1 to k10 are the coefficients provided in standard;
lg is log10.
Coefficients for the further calculations are in reference to IEEE 1584-2018. Particular values for this validation case scenarios are provided at Annex No.1 Calculation coefficients.
According to IEEE 1584-2018, intermediate arcing currents for 600 V, 2700 V and 14 300 V must be calculated as follows:
Then accordingly arcing currents are calculated as follows:
Then arcing currents are:
The final arcing current for Voc > 2,7 is:
Then arc duration is determined using I_arc from a power fuse time current characteristic (TCC). In this case, arc duration is:
Enclosure size correction factor
Based on Enclosure type (Typical) and dimensions, equivalent width is calculated:
Equivalent height:
Thus, equivalent enclosure size value is:
The correction factor for a VCB electrode configuration is:
Intermediate values of incident energy
Intermediate values of incident energy are calculated using coefficients that are in reference to IEEE 1584-2018.
Thus, intermediate incident energy for 600 V:
Intermediate
incident energy for 2700 V:
Intermediate incident energy for 14300 V:
The final incident energy is:
Arc Flash boundary
Intermediate values of arc-flash boundary are calculated using coefficients that are in reference to IEEE 1584-2018.
Thus, intermediate arc-flash boundary for 600 V is calculated from equation:
Intermediate arc-flash boundary for 2700 V:
Intermediate arc-flash boundary for 14300 V:
The final value of arc-flash boundary is determined:
The final arc-flash boundary is:
Calculations using EA-PSM are performed for the test scheme that is depicted at Figure 1. Conductor configuration and enclosure parameters are defined at Bus properties (Figure 2), while protection device parameters are defined depending on device.
Calculation results are presented at the EA-PSM table and can be exported to .xlsx file format.
EA-PSM also allow to print a warning label for required safety measures such as presented at Figure 3.
Results comparison between validation calculations based on IEEE 1584-2018 standard [1] and calculations performed using EA-PSM are depicted at Table 2.
Difference between validation calculations based on IEEE Std 1584-2018 and EA-PSM calculations differ insignificantly by not more than 0.51%.
As shown by this test case, EA-PSM is a reliable tool for correctly calculating Arc flash parameters.
IEEE Std 1584-2018
IEEE Guide for Performing Arc-Flash Hazard Calculations
Scheme link element is dedicated to dividing the scheme into logical blocks thus reducing graphics lag and allowing to calculate equivalents
This feasibility study carries out calculations needed to connect a solar power plant to a low voltage grid following IEC standards
Receive our latest weekly releases, offers, guides and more.
© 2023 EA-PSM All rights reserved.
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics". |
cookielawinfo-checkbox-functional | 11 months | The cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional". |
cookielawinfo-checkbox-necessary | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary". |
cookielawinfo-checkbox-others | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other. |
cookielawinfo-checkbox-performance | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance". |
viewed_cookie_policy | 11 months | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data. |
Fill out the given form to view the whole post
Confirm your email to get access to our news.